Ultra Isolation Transformers

  • Low inter-winding capacitance
  • Good DC galvanic isolation
  • High attenuation – 100 dB in common mode up to 10 kHz
  • Optimum transformer design ensures good load regulation
Parameter Single-Phase 2-Phase to 1-Phase
Rating 1kVA to 10kVA 1kVA to 25kVA
Reference Standard IS 11171 : 1985 (Reaffirmated 2006)
Type of Transformer Floor mounted, natural air-cooled / oil-cooled (depending on rating) Dry type, floor mounted, natural air-cooled
Configuration Delta / star 1:1        (or as per user specification) 1:1 (or as per user specification)
Default Vector Group Dyn11
Type of lamination CRNO
Winding Copper Wire / Strip or Aluminium wire / strip
Load Regulation Better than 3%
Class of insulation Class H
Efficiency 3 – 12 kVA (>95%)
> 15 kVA (>97%)
At rated input voltage and at 100% rated current of loads that are linear
Insulation Strength Withstands 2.5 kV for 1 minute (between windings & between windings and body)
DC galvanic isolation > 1000 Mega Ohms – for UIT
> 100 Mega Ohms – for GIT
Common Mode noise rejection (for UIT only) Up to 10kHz > 100 dB 10 kHz to 50 kHz > 60 dB 50 kHz to 1 MHZ > 40dB
Short Circuit Protection HRC fuse at input provided as a standard / MCB / MCCB can be provided as an option
Indications LED Lamps for Output Presence Digital Voltmeter (DVM) – optional
Housing Sheet metal housing provided with Input / Output terminations